How Is the Battery Rating of a Diesel Generator Calculated?

Table of Contents

After years of supplying diesel generator sets for export projects, I’ve noticed one thing very clearly: battery selection is often treated as an afterthought, even though it directly affects whether a generator starts reliably or not.

In practice, many generators that “meet all specifications” still fail at the most basic task—starting. And when that happens, the root cause is often the battery.

A diesel generator’s battery rating is not determined by generator kVA, but by the engine’s starting requirements and the operating environment.

Below, I’ll explain how I evaluate battery rating in real projects—and where buyers commonly get it wrong.

What “Battery Rating” Actually Means for a Diesel Generator

When people ask about battery rating, they usually refer to:

  • Battery voltage (12V or 24V)
  • Battery capacity (Ah)
  • Cold Cranking Amps (CCA)

From real-world experience, CCA is far more critical than Ah for diesel generators.

Diesel engines don’t fail to start because they lack stored energy over time.
They fail because the battery cannot deliver enough current instantly to overcome compression and crank the engine.

Step 1: Determine the Starting Voltage (12V vs 24V)

In export projects, I apply a very practical rule:

  • Small diesel generators (typically below 30–40 kVA)
    → 12V starting system (single battery)

  • Medium to large industrial generators
    → 24V starting system (two 12V batteries in series)

This isn’t a preference—it’s driven by starter motor torque requirements. Larger engines demand higher starting torque, and 24V systems improve reliability while reducing cable losses.

If I see a large industrial diesel generator configured with a 12V starting system, I treat that as a warning sign.

Step 2: Size the Battery Based on the Starter Motor, Not kVA

This is where many buyers make a fundamental mistake.

They ask:

“This is a 100 kVA generator - what battery does it need?”

That question skips the most important factor: the starter motor.

What I actually look at is:

  • Starter motor power (kW)
  • Starter motor rated current
  • Engine displacement and compression ratio

Two generators with the same kVA rating can require very different battery performance depending on the engine design.

In practice, reputable engine manufacturers specify:

  • Minimum required CCA
  • Recommended battery range

Ignoring this and sizing batteries purely by generator kVA is one of the most common reasons for starting failures in the field.

Step 3: Adjust Battery CCA for Ambient Conditions

This is where real project experience matters most.

A battery that works perfectly in a warm climate may fail repeatedly in cold regions—even if the generator itself is correctly sized.

My rule of thumb:

  • Warm or tropical environments
    → Standard CCA specification is usually sufficient

  • Cold climates or high-altitude sites
    → I increase CCA beyond the minimum, often by 20–30%

Cold temperatures significantly reduce effective battery output. I’ve seen multiple export projects where generators failed to start in winter simply because the battery specification was copied from a warm-climate installation.

Why Ampere-Hour (Ah) Rating Is Secondary

Ampere-hour rating mainly affects:

  • How many start attempts are possible
  • How long control systems can operate without charging

In real applications, I rarely see generators fail because Ah capacity is slightly undersized—as long as CCA is sufficient and the charging system is working properly.

This is why I don’t select batteries based on Ah alone, and I don’t recommend others do either.

Common Battery Selection Mistakes I See in Export Projects

Based on actual cases, these are the most frequent errors:

  • Selecting battery size based on generator kVA
  • Ignoring starter motor specifications
  • Using automotive-grade batteries with low CCA
  • Failing to adjust specifications for cold or remote environments
  • Assuming higher Ah automatically means better starting performance

A battery with high Ah but insufficient CCA can still fail to start a diesel engine.

How I Evaluate Battery Selection in Practice

When reviewing or specifying a generator battery, I make sure:

  • Battery voltage matches the engine starting system (12V or 24V)
  • CCA meets or exceeds engine manufacturer requirements
  • Battery is an industrial starting battery, not a passenger vehicle type
  • Battery specification reflects local climate conditions, not copied defaults

This approach has proven reliable across telecom backup systems, industrial standby installations, and long-term export projects.

Conclusion

The correct battery rating for a diesel generator is determined by engine starting demand and operating environment - not by generator kVA or battery capacity alone.

Understanding this distinction prevents many of the starting failures that only appear after installation, often when the generator is needed most.

If you're looking past datasheets and thinking about real-world reliability, battery selection is one of the easiest places to get it right.

Facebook
Twitter
LinkedIn
Pinterest
Picture of Ke Wong

Ke Wong

Hey, I’m Ke Wong joined WALT POWER in 2011. I spent a dozen years focused on generator set & load bank technology and solutions for the power & energy industry. WALT Power is a reliable & leading manufacturer & supplier in China, as a business director, I am so proud of our knowledge is more and more popular not only for engineers, and generator distributors but also for end-users. Hope you are enjoying our article, if any questions or comments welcome to send me sales at waltpower.com